>> fentonups (8) ( Linux man: Команды системного администрирования )
NAME
fentonups - Driver for Fenton Technologies (Megatec protocol) UPS equipment
NOTE
This man page only documents the hardware-specific features of the
fentonups driver. For information about the core driver, see
nutupsdrv(8).
SUPPORTED HARDWARE
fentonups primarily supports Fenton Technologies models such as the
PowerPal, PowerPure and PowerOn lines. Due to the common heritage of UPS
equipment, it also supports other hardware that also uses the Megatec
protocol.
At the time of this writing, the PowerGuard PG-600 and PowerCom SMK-800A
are recognized and supported. Other Megatec units should also work, but
they will generate a warning since their battery information is not known.
EXTRA ARGUMENTS
This driver does not support any extra values for -x or in the
ups.conf(5).
BUGS
The battery percentage is derived from the voltage data that the UPS
returns, since the UPS doesn't return that value directly. On some
hardware, the charge will remain at 100% for a long time and then drops
quickly shortly before the battery runs out. You can confirm from the
BATTVOLT readings that this is a problem with the UPS and not this driver.
Similarly, the float from the charger in some models forces the battery
charge percentage back up to 100% immedately after the UPS goes back
on-line, so you can't tell when it is really recharged.